Voltage Monitoring Relays
Frequency Monitoring Relays
Power Monitoring Relays & CBCT
Level Controllers – Conductive Liquids
Level Controllers – Non Conductive Liquids
Process/Plant Control and Automation
Twin AC Controller

Alarm Annunciators

MBAS 11

Potential Fault Inputs of 110 VDC or 220 VDC

LED base Annunciator

Technical Data

  • Supply Voltage 90 to 270 V AC/DC
  • Supply Frequency50 / 60 Hz ± 3%
  • Windows16 Fixed
  • Display (Window)Single LED Type
    Legend Window Dimension (H X L)
  • Legend Window Dimension (H X L) 06 X 26 mm
  • Flash Rate50 to 60 Flash / min.
  • LegendsPre Printed Positive on Paper
  • Facia TypeFront Replaceable
  • LED ColourRED only
  • Input Signal (For Fault)110 V DC / 220 V DC ± 20 (with -ve common)
  • Interrogation Voltage (For Keys)(+) 12 V DC
    Output Contacts Three Opto Isolated Electromagnetic Relay
  • 1 NO (for Hooter)
  • 1 NO (for Group Fault)
  • 1 NC (for Supervisory Contact)
  • Output Contact Rating5 Amp. 240 V AC (Resistive)
  • ArchitectureIntegral
  • Operational Sequences 1. Manual Reset (S1) with Lamp Test having Group Relay (Fixed) alarm feature. Grouping is Fixed. Fixed NO type.
    OR.
    2. Auto Reset (S2) with Lamp Test having group relay (Fixed) alarm feature. Grouping is Fixed. Fixed NO type (Factory Set)
  • Operational Temp0 ˚C to 60 ˚C
  • Storage Temperature-10 ˚C to +70 ˚C
  • HumidityUpto 96% Rh
    Dimensions (mm)
  • Over All (H X W X D)96 X 96 X 108 mm
  • Cutout (H X W)92 X 92 mm

Applications

GIS panels

C & R Panels

CONTACT

Delhi
delhi@minilecgroup.com

Kolkata
kolkata@minilecgroup.com

Mumbai
mumbai@minilecgroup.com

Bangalore
bangalore@minilecgroup.com