MBAS 11

Potential Fault Inputs of 110 VDC or 220 VDC

LED base Annunciator

Technical Data

  • Supply Voltage 90 to 270 VAC/DC
  • Supply Frequency50 / 60 Hz ± 3%
  • Windows16 Fixed
  • Display DeviceSingle LED Type
    Legend Window Dimension (H X L)
  • Legend Window Dimension (H X L) 06 X 26 mm
  • Flash Rate50 to 60 Flash / min.
  • LegendsPre Printed Positive on Paper
  • Facia TypeFront Replaceable
  • LED ColourRED only
  • Input Signal (For Fault)110 V DC / 220 V DC ± 20% with -ve common
  • Interrogation Voltage (For Keys)+ 12 V DC
    Output Contacts Three Opto Isolated
  • 1 NO for Hooter
  • 1 NO for Group Fault
  • 1 NC for Supervisory Contact
  • Output Contact Rating5 Amp. @ 240 V AC (Resistive)
  • ArchitectureIntegrated
  • Operational Sequences 1. Manual Reset (S1) with Lamp Test having Group Relay (Fixed) alarm feature. Grouping is Fixed. Fixed NO type.
    OR.
    2. Auto Reset (S2) with Lamp Test having group relay (Fixed) alarm feature. Grouping is Fixed. Fixed NO type (Factory Set)
  • Operational Temp0 - 60 ˚C
    Dimensions (mm)
  • Over All (H X W X D)96 X 96 X 108
  • Cutout (H X W)92 X 92

Applications

GIS panels

C & R Panels

CONTACT