Motor / Pump Protection Relays
PGS D2
Single Phase Over Load & Dry Run protection Relay suitableup to 10 Amps.
Relay Output 1CO / 2 CO
Auto / Manual / Remote Reset.
Technical Data
Supply Voltage
- System 220-240 VAC ± 20 %, 50/60 Hz ± 3%
Output Relay Contact
- Output Relay Contact 1CO / 2CO
Input
- Input Build in CT 10A /5A (SELECTABLE)
Trip Setting
- Phase to phase unbalance N.A.
- Under current (Dry running)75% of set current ± 10% (fixed)
- OverloadAbove 120% of set Current (fixed)
- UV/OV N.A.
Trip Time Delay
- On phase failure Less than 2 sec
- For overloading As per 2 sec. Inverse Time current characteristics
- UV/OV RP N.A
Resetting
- ResettingAuto / Manual / Remote
Approx Weight
- Approx Weight600 gms
Dimensions (mm)
- Overall (L x W x D) 76 x 56.5 x 117.5
- Mounting (L x W)67 x 46 /35 mm Rail Mounting