MBAS 08

Most compact alarm Annunciator with improved window design and all major features of MBAS 0600 Annunciator. Models with built-in Buzzer & Push buttons also available.

Technical Data

  • Supply Voltage 90 to 270 VAC/DC
    24 VDC /30 VDC /48VDC
  • Supply Frequency [FOR AC]50 / 60 Hz ± 3%
  • Windows4 / 6 / 7 / 8 [max]
  • Display (Window)Window lenses replaceable Legends replaceable.
    Window Dimensions
  • Small 37 X 17 mm
  • Big 37 X 27 mm. for 4 Windows model only
  • Power Consumptions1.5 Watts per Window (Max)
  • Flash Rate50 - 60 Flash per min. in fast flashing
    20 - 30 Flash per min. in slow flashing
  • Operating SequenceS1, S2, S3 (Optional), S4 (Site Selectable)
  • Other FeaturesNO / NC and Grouping (Trip/Non trip) Selection
    Supervisory Contact output.
  • Optional FeaturesAny other operating sequence
    RS232 / RS485 Output
    Man / Unmanned Feature
    Supply fail Annunciation
  • Input SignalPotential Free contacts
  • Input Interrogation Voltage+12 VDC
  • LED Colour in WindowsRed, Green, Yellow (Amber), Blue, White.
  • Output Contacts1 NO + 1 NO [For Hooter]
    1NO For Ring back or Supervisory contact (Optional)
  • Output Contact Rating5 Amp, 240V AC (Resistive)
  • Inbuilt Push Buttons4 NOS. (Test, Mute, Accept, Reset) Membrane type (Optional)
  • CommunicationRS232 / RS485 (MODBUS RTU/ASCII) (Optional)
  • Operational Temp. Limit-5°C to 60°C
  • HumidityUpto 95% Rh
  • EnclosureABS moulded enclosure
    Unit Dimensions
  • Overall (L x W x D)96 x 96 x 76 mm
  • Cutout (L x W)92 x 92 mm
  • Weight350gm
PROGRAMMING OF MBAS 08
SR. NO. KEY OPERATION MODE OF OPERATION WINDOW STATUS WDL STATUS
1 --- Normal Run Mode As per operation Flashing @ 1 flash/sec.
2 TEST + ACK
Pressed (for 5 Sec.)
Sequence selection Windows
fast flashes for
2 to 3 sec.
W1 - ON - S1
W2 - ON - S2
W3 - ON - S3
W4 - ON - S4
Flashing @ 1 flash/sec.
3 TEST + ACK
Pressed (for 5 Sec.)
NO / NC selection W - ON - NO
W - OFF- NC
Off
4 TEST + ACK
Pressed (for 5 Sec.)
Grouping selection W - ON - Group 1
W - OFF- Group 2
Steady On
5 TEST + ACK
Pressed (for 5 Sec.)
Device ID selection As per chart in Manual Fast Flashing
6 Auto exit after 5 Seconds

Applications

Instrumentation Panel

Control Rooms

C & R Panel

Plants, Diesel Generators

Transformer Panel

Material handling Systems