D3 PTF1

Frequency transducer

Output (DC) single or dual

Accuracy 0.5%

Operations
The input frequency signal is scaled down through Interposing potential transformer. The scaled down signal is fed to a precision frequency to voltage Converter stage, its output is processed to provide DC Voltage/ Current proportional to Line Frequency.

Technical Data

    Auxiliary Supply
  • Auxillary 24/48V DC+/-20%, Self Powered, 80-300VAC/ DC,50 Hz
    Power Consumption
  • Power Consumption 3.5 VA - AC, 4 VA - DC
    Input Value
  • I inFreq. Range 45 to 55 Hz/40-60 Hz/55-65 Hz/48-52Hz
  • V in63.5/110/240/415 V
    DC Output (Single / Dual)
  • DC Output (Single / Dual) 0 - 1 mA, 0 - 10 mA, 0 - 20 mA, 4 - 20 mA, 0 - 5 V, 0 - 10V DC Other optional on request
    No of Signal Output
  • No of Signal Output Single (Optional Dual Output)
    Response Time
  • Response Time Less than 500 milliseconds
    Input / Output isolation
  • Input / Output isolation Galvanic
    Temperature
  • Temperature 0°C to + 55°C
    Humidity
  • Humidity Up to 95% Rh non condensing
    Dimensions (L x W x D) (mm)
  • Dimensions (L x W x D) (mm) 75 x 56.5 x 117.5
    Weight
  • Weight 575 gms

    Common Specifications

    Output Load Resistance (Rout)
  • For Current Output Max. 10V/I out (Optional Max. 15V/Iout)
  • For Voltage Output10 Kohm (min.)
    Output Ripple
  • Output Ripple Less than 0.5% of span (peak to peak)
    Auxiliary Supply Burden
  • Auxiliary Supply Burden Less than 4 VA
    Insulation Resistance
  • Insulation Resistance More than 100 Mohms at 500 V DC
    Zero Span Adjustment
  • Zero Span Adjustment Optionally provided
    Terminals
  • TerminalsSuitable for 2.5 sq.mm wires
    Enclosure Type
  • Enclosure Type ABS Plastic, Ingress Protection IP40
    IEC Standard
  • IEC Standard 60688

Applications

Instrumentation Panel.

Generator Panels.