Voltage Monitoring Relays
Frequency Monitoring Relays
Power Monitoring Relays & CBCT
Level Controllers – Conductive Liquids
Level Controllers – Non Conductive Liquids
Process/Plant Control and Automation
Twin AC Controller

Phase Failure Relays

ALV D2

ALV D2 Phase Failure Relays - Minilec Group

Technical Data

    Supply Voltage
  • System 110 / 240 / 380 / 415 / 440 V AC ±20% 50 / 60 Hz
  • Auxillary 110 V (Fixed) or (220 - 230 - 240) or (380 - 415 - 440) V AC ±20% selectable
    Output Contacts
  • Output Contacts2 CO
    Trip Setting(Volts)
  • Phase SequenceYes
  • Phase Unbalance40 V ±6 V (fixed)
  • Under VoltageFor 380-440V AC
    For 220-240V AC
    For 110 V AC
    80% to 95% (adjustable) of auxillary supply (±2% of set value)
  • Under VoltageFor 380-440V AC
    For 220-240V ACFor 110 V AC
    105% to 120% (adjustable) of auxillary supply (±2% of set value)
    Trip Time Delay
  • On Phase Failure3.5 secs. ± 1.5 sec
  • On UV/OV Less than 2 secs.
    Resetting Mode
  • Resetting Mode Auto Reset
    Weight
  • Weight400 gms.
    Dimensions (mm)
  • Overall (L x W x D)76 x 56.5 x 117.5
  • Mounting (L x W)67 x 46 alt / 35 mm rail Mounting
    Note:
  • Wherever not specified Contact Rating : 5A @ 230 V AC (resistive)
  • * CE marked products available on request.

Applications

AC & R Chiller compressor motors

AHU Fan /Pump Motors

Hoist & Crane

Machinery using multiple small motors

MAIN powers supply distribution panel board

DG Set application

Submersible Pumps

UPS

CONTACT

Delhi
delhi@minilecgroup.com

Kolkata
kolkata@minilecgroup.com

Mumbai
mumbai@minilecgroup.com

Bangalore
bangalore@minilecgroup.com