- Phase Failure Relays
- Monitoring Relays
- Motor / Pump Protection Relays
- Electronics Timers
- Liquid Level Controllers
- Power Line Transducers And MFM
- Automation Products
- Alarm Annunciators
- Products For Agri Sector
Potential Free Inputs
Potential Inputs
Alarm Annunciator
Power Line Transducers And Multifunction Meter
D5 PAT1

Precision grade transducer used for measurement of Phase Angle between Voltage and Current Waveforms of a 3 Phase 3 Wire or 3 Phase 4 Wire Electrical Network System.
Technical Data
- Auxiliary Supply 110/240 V AC ± 15%, 24/48/110/220 VDC ± 10%, 18-60 V DC, 80-300 VAC/DC, 50Hz Self Powered
Supply Voltage
- Power ConsumptionLess Than 4 VA - DC
- Input Value
- I in1 or 5 A AC
- V in110 V AC (HT Supply), 415 VAC (LT Supply)
- Resistance Type3 Wire, 4 Wire
- DC Output (Single / Dual)4-20 mA DC,0-1,0-5,0-10,0-20 mA DC, 0-(+)5 0-(+)10,0-(+)20 mA DC, 0-5,0-10 VDC
- No of Signal Output Single (Optional Dual Output)
- Response Time Less than 500 milliseconds
- Input / Output Isolation 2 KV 50 Hz for 1 min
- Temperature0°C to + 55°C
- HumidityUp to 95% Rh non condensing
- Dimensions (L x W x D) (mm)150 X 70 X 114
- Weight1200 gms.
Common Specifications
- Output Load Resistance (Rout)
- For Current OutputMax. 10V/I out (Optional Max. 15V/Iout)
- For Voltage Output10 Kohm (min.)
- Output RippleLess than 0.5% of span (peak to peak)
- Auxiliary Supply BurdenLess than 4 VA
- Insulation ResistanceMore than 100 Mohms at 500 V DC
- Zero Span AdjustmentOptionally provided
- TerminalsSuitable for 2.5 sq.mm wires
- Enclosure TypeABS Plastic, Ingress Protection IP40