Motor / Pump Protection Relays
D2 MPR2


Under & Over Voltage
Overload & Dry Run, Unbalance
Manual Reset, Delayed Auto Reset
Sensing both Voltage and Current Signals
Phase Failure, Phase Sequence
Fixed Trip Settings
Fixed Overload Characteristics
2 CO Output Relay
Technical Data
- Auxiliary 220-240 / 380-415 V AC ± 20%, 48 - 63 Hz
Supply Voltage
- Output Relay Contact 2 CO
Output Relay Contact
- Input From S2 CTS 1
Input
- Phase to phase unbalance 50% of Motor Current (fixed)
- Under Current (Dry Run)50% of Set Current (fixed)
- OverloadAs per IDMTL Characteristics
- UV/OV UV = -20% (fixed) OV = +20% (fixed)
Trip Setting
- Phase Failure, Unbalance, Dry Run 4 Sec ± 1%
- OverloadAs per IDMTL Characteristics 2 Sec. (Fixed)
- UV/OV RP For UV/OV - 4 Sec ± 1 Sec | RP - Less than 2 Sec.
Trip Time Delay
- ResettingDelayed Auto/ Manual
Resetting
- Approx Weight400 gms
Approx Weight
- Overall (L x W x D) 76 x 56.5 x 117.5
- Mounting (L x W)67 x 46 / 35 mm Rail Mounting
Dimensions (mm)
- Wherever not specified Contact Rating: 5A @ 230 V AC (resistive)
Note: