Motor / Pump Protection Relays
D2 MPR3

Overload & Dry Run, Unbalance
Auto/Manual Reset
Testing
Facility
UC Bypass Facility
Phase Failure, Phase Sequence
Adjustable Trip Settings
Selectable Overload Characteristics
2 CO Output
Relay
Technical Data
- Auxiliary 100 - 120 / 220 - 240 / 380 - 440 V AC ± 20%,
48 - 63 Hz
Supply Voltage
- Input from S2 CTS 1
Input
- Output Contacts2 CO
Output Contacts
- Phase to Phase Unbalance 50% of Motor Current ± 10% (Fixed)
- Under Current (Dry Run)40% to 80% ± 5% of Set Current (Adjustable with Bypass Facility)
- Over LoadAs per IDMTL Characteristics
Trip Setting
- On Phase Failure4.0 Sec ± 1.0 Sec
- Over Load As per IDMTL Characteristics 2 Sec. (Fixed)
Trip Time Delay
- Reset Auto / Manual / Remote
Resetting Mode
- Weight250 gms (Approx.)
Weight
- Overall (L x W x D)76 x 56.5 x 117.5
- Mounting (L x W)67 X 46 / 35 mm Rail Mounting
Dimensions (mm)
- Wherever not specified Contact Rating : 5A @ 230 V AC (resistive)