Phase Failure Relays
S2 VMR3
Microcontroller design
SMD Technology
Absolute values of UV/OV settings
Phase Failure, Unbalance
Phase Sequence, under voltage
Over Voltage, Auto/Manual reset
Adjustable settings for Unbalance
UV/OV and trip delays
2 CO output relay, failsafe-non-failsafe Selectable
Microcontroller design
SMD Technology
Absolute values of UV/OV settings
Technical Data
- System 100-120 / 220-240 / 380-440V AC -25%+20%, 48-63 Hz
- Auxillary Built In (from 3 Phase)
Supply Voltage
- Output Contacts2 CO
Output Contacts
- Phase SequenceYes
- Phase Unbalance4 % - 20 % [Variable]
Trip Setting(Volts)
- Under VoltageFor 380-440V AC
For 220-240V AC
For 100-120V AC285-425V AC [Variable]
165-225V AC [Variable]
75-115V AC [Variable] - Over VoltageFor 380-440V AC
For 220-240V AC
For 100-120V AC400-520V AC [Variable]
230-290V AC [Variable]
105-145V AC [Variable]
- On Phase FailureInstant
- On UV/OV 1 To 10 Sec [Variable]
Trip Time Delay
- Resetting Mode Auto/ Manual Reset [Selectable]
Resetting Mode
- Weight110 gms.(Approx)
Weight
- Overall (L x W x D)90 X 35 X 60
- Mounting (L x W)35 mm Rail Mounting
Dimensions (mm)
- products available on request - P2 PFV1, P2 SMV1