- Phase Failure Relays
- Monitoring Relays
- Motor / Pump Protection Relays
- Electronics Timers
- Liquid Level Controllers
- Power Line Transducers And MFM
- Automation Products
- Alarm Annunciators
- Products For Agri Sector
Motor / Pump Protection Relays
S2 CMR1
Phase Failure
Phase sequence, Unbalance
Overloading and dry running (Under current) Microcontroller based design
SMD technology
Auto/Manual Reset
Adjustable current trip settings
Selectable overload characteristics
2 CO output relay
Technical Data
- Auxillary 100-120/220-240/415 VAC±20%, 24V DC+10%-15%
Supply Voltage
- Output Relay Contact 2 CO
Output Relay Contact
- Input From S2 CTS
Input
- Phase to phase unbalance 50% of Motor Current (Fixed)
- Under current (Dry running)40% to 80% of set current (Adj. with bypass facility)
- OverloadAs per inverse time characteristics
- UV/OV N.A.
Trip Setting
- On phase failure 4 Sec ± 1% Sec (Fixed)
- For overloading As per Inverse Time Characteristics 2/5/10 Sec. (Selectable)
- UV/OV RP N.A.
Trip Time Delay
- ResettingAuto / Mannual
Resetting
- Approx Weight140 gms
Approx Weight
- Overall (L x W x D) 90 x 35 x 60
- Mounting (L x W)35 mm Rail Mounting
Dimensions (mm)
- Wherever not specified Contact Rating: 5A @ 230 V AC (resistive)