banner_phase_failure_relays


 
Products I Power Line Transducers I D3 RET1



D3 RET1
Resistance transducer
Input 2 Wire or 3 Wire Resistance output (DC) single or dual
Accuracy 0.5%

Operations

It is a precision grade transducer is used for galvanically isolated measurement of Transformed Tap or Resistance (2 Wire or 3 Wire). It measures the value of resistance on tap position changers, typically used on high voltage transformers. Each position on the selector has an equal value of resistance so that as the tap position is increased or decreased the value of resistance increases or decrease respectively. The input is in the form of Resistance and provides a Stable, Ripple- Free and Optically Isolated DC load independent output in the form of current or voltage. The transducer is fully solid state. Use of latest circuit techniques and quality components ensure reliable operation over long period.
Auxiliary Supply : 110/240 V AC (+/-) 20%,50 Hz / 60Hz
24/48/110/220 V DC (+/-)20%
60 – 300 V AC / DC

Power Consumption : Less than 4 VA

Input Value
I in
V in
:
:
As per given range, e.g. 0 - 100 Ohm, 0 - 200 Ohm, 0 - 1KOhm
-

Resistance Type : 2 Wire, 3 Wire

DC Output (Single / Dual) :
0 – 1 mA DC, 0 – 5 mA DC, 0 – 10 mA DC, 0 – 20 mA DC, 4 – 20 mA DC, (-)20 – 0 - (+)20 mA DC, 4 – 20 mA DC, 500 Ohm (max), 0 – 5 V DC, 0 - (+)10 V DC, (-)10 – 0 - (+)10 V DC

No of Signal Output : One No., Two Nos.

Response Time : Less than 500 mSec.

Input / Output Isolation : 2 KV 50 Hz for 1 min

Temperature : 0 – 55°C.

Humidity : 95% RH Non-condensing

Dimensions (L x W x D) (mm) : 85 X 80 X 120

Weight : 350 gms
Electrical Connection Diagram
D3 RET1
Suitable for Panels in Following Apllications:
Measurement Panel.
Test Equipments.
 
 
 
 



Voltage, Current, Frequency Transducers

Power Transducers

Isolation Transducers