Frequency transducer
Output (DC) single or dual
Accuracy 0.5%

Operations

The input frequency signal is scaled down through Interposing potential transformer. The scaled down signal is fed to a precision frequency to voltage Converter stage, its output is processed to provide DC Voltage/ Current proportional to Line Frequency.
Auxiliary Supply : Self Powered, 110/240 V AC ±20%
24 / 48 / 110 / 220 V DC ±20%

Power Consumption : 3.5 VA - AC, 4 VA - DC

Input Value
I in
V in
:
:
Freq. Range 45 to 55 Hz/40-60 Hz/55-65 Hz/48-52Hz
63.5 / 110 / 240 / 415 V

DC Output (Single / Dual) :
0 - 1 mA, 0 - 10 mA, 0 - 20 mA, 4 - 20 mA, 0 - 5 V, 0 - 10 V Other optional on request

No of Signal Output : Single (Optional Dual Output)

Response Time : Less than 500 milliseconds

Input / Output isolation : Galvanic

Temperature : 0°C to + 55°C

Humidity : Up to 95% Rh non condensing

Dimensions (L x W x D) (mm) : 75 x 83.5 x 117.5

Weight : 575 gms

Common Specifications

Output Load Resistance (Rout)
For Current Output
For Voltage Output
:
:
Max. 10V/I out (Optional Max. 15V/Iout)
10 Kohm (min.)

Output Ripple :
Less than 0.5% of span (peak to peak)

Auxiliary Supply Burden : Less than 4 VA

Insulation Resistance : More than 100 Mohms at 500 V DC

Zero Span Adjustment : Optionally provided

Terminals : Suitable for 2.5 sq.mm wires

Enclosure Type : ABS Plastic, Ingress Protection IP40
Electrical Connection Diagram
D3 PTF1

Note: Voltage/Current Transducer in case of dual output will come in D3 enclosure (Dimension change)
Generator Panels.
Instrumentation Panel.
Control Panels in Power Plant.
 
 
 
 



Voltage, Current, Frequency Transducers

Power Transducers

Isolation Transducers

Transducers Models