Products I Power Line Transducers I D3 IST1



D3 IST1
Signal Isolation transducer
Input & output DC signals
Single or dual outputs
Accuracy 0.5%

Operations

The input signal is filtered and processed to convert into a standard dc voltage. This voltage is fed to a linear optocoupler which provides the required galvanic isolation. An optical feedback is used for improved linearity, response time and temperature effects. The output from the linear optocoupler is further processed to provide dc voltage / current output.

The isolator with fast response time (10 mSec) are typically used in feedback control system.

In input dc current is chopped by the chopper to convert it into high frequency ac signal. This signal is fed to an isolating high frequency transformer. The ac output current from the transformer is rectified and filtered to obtain load independent dc output current. As the transformation ratio is 1:1 the output current is identical in value to the dc input current.
Auxiliary Supply : Self Powered, 110/240 V AC, 24 / 48 / 110 / 220 V DC ± 20 %

Power Consumption : 3.5 VA - AC, 4 VA - DC

Input Value
I in
V in
:
:
0-1, 0-5, 0-10, 0-20, 4-20mADC Signals
0-50, 0-60, 0-75, 0-100 mV DC / 0-1, 0-5, 0-10, 0-150, 0-300, 0-600 V DC

Resistance Type N.A.

DC Output (Single / Dual) :
0 - 1 mA, 0 - 10 mA, 0 - 20 mA, 4 - 20 mA, 0 - 5 V, 0 - 10 V

No of Signal Output : Single (Optional Dual Output)

Response Time : 500 mSec.

Input / Output isolation : Galvanic

Temperature : 0°C to + 55°C

Humidity : Up to 95% Rh non condensing

Dimensions (L x W x D) (mm) : 73 x 83.5 x 117.5

Weight : 1200 gms.
Electrical Connection Diagram
D3 IST1
Suitable for Panels in Following Apllications:
Instrumentation Panels
Control Desk
PLC / DCS / SCADA Automation Systems
Measurement & Control Panels
 
 
 
 



Voltage, Current, Frequency Transducers

Power Transducers

Isolation Transducers