Home  |  Contact Us

banner_phase_failure_relays


 
Products I Monitoring Relays I D2 VCT1



D2 VCT1
  3-Phase 3-Wire and 3-Phase 4-Wire (selectable) Under & Over voltage,
  Microcontroller based design,
  Auto/Manual Reset,
  Adjustable under/over voltage settings,
  Absolute values for UV/OV,
  Adjustable trip delay & ON delay,
  2 CO output relay (or selectable 1CO for UV, 1CO for OV) Failsafe-non-failsafe selectable
System Supply : 100-120/220-240/380-440V AC -25%+20%,48-63 Hz

Output Relay Contacts : 1 CO + 1 CO / 2 CO

Trip Setting    
  Under
Voltage
Ph Ph Setting:
For 380-440V AC
For 220-240V AC
For 100-120V AC
Ph N Sensing:
For 380-440V AC
For 220-240V AC
For 100-120V AC

:
:
:

:
:
:

285-425V AC (Variable)
165-225V AC (Variable)
75-115V AC (Variable)

165-245V AC (Variable)
95-135V AC (Variable)
45-65V AC (Variable)
  Over
Voltage
Ph Ph Sensing:
For 380-440V AC
For 220-240V AC
For 100-120V AC
Ph N Sensing:
For 380-440V AC
For 220-240V AC
For 100-120V AC

:
:
:

:
:
:

400-520V AC (Variable)
230-290V AC (Variable)
105-145V AC (Variable)

230-310V AC (Variable)
130-170V AC (Variable)
60-80V AC (Variable)

Trip Time Delay : 1-10 Sec (Variable) UV/OV/NF

Power on Delay : 1-10 Sec (Variable)

Reset : Auto / Manual Reset

Weight : 300 gms. (Approx.)

Dimensions (mm)
  Overall (L x W x D) : 76 x 56.5 x 117.5
  Mounting (L x W) : 67 x 46    / 35 mm rail Mounting

Note:
Wherever not specified Contact Rating : 5A @ 230 V AC (resistive)
Timing/ Relay logic Diagram

Electrical Connection Diagram

D2 VCT1 D2 VCT1

Relay contact position shown in 'Power off' condition
Auto Mains Failure Panels.
Generator Set Panels.
Battery Charger Panels.
Inverter Panels.
DC Drive Control panels.
UPS
 
 
 
 



MODELS

Voltage Monitoring Relays

Current Monitoring Relays

Ground Fault Monitoring Relays

Frequency Monitoring Relays

Power Monitoring Relays